Customization: | Available |
---|---|
Phase: | Single Phase |
Type: | On-line |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Model(EX series ups) | EX1K | EX1KL | EX2K | EX2KL | EX3K | EX3KL | |
Capacity | 1000VA/800W | 2000VA/1600W | 3000VA/2400W | ||||
Input | Voltage | 115~300VAC | |||||
Frequency | 46~54Hz/56~64Hz/Adjustable via LCD panel | ||||||
Output | Voltage | 220/230/240/1±1%VAC(Adjustable via LCD panel) | |||||
Frequency | 50/60Hz(Adjustable via LCD panel) 50Hz AC Mode--Follow AC Mode(AC Range 46~54Hz) Battery Mode--50Hz(1±0.2%) 60Hz AC Mode--Follow AC Mode(AC Range56~64Hz) Battery Mode--60Hz(1±0.2%) |
||||||
Output Wave Form | Sine Wave | ||||||
Back-up Time | Full Load | ≥5′ | Depends on the capacity of the external battery bank | ≥9′ | Depends on the capacity of the external battery bank | ≥5′ | Depends on the capacity of the external battery bank |
Half Load | ≥14′ | ≥21′ | ≥15′ | ||||
BatteryNominal DC Voltage | 36VDC | 96VDC | |||||
Transfer Time | 0ms | ||||||
Overload Capacity | 110%~150% maintain 30s then turn to bypass output, over 150% maintain 300ms | ||||||
Communications | RS-232+Intelligent Slot | ||||||
Environment | Temperature | 0c~40c | |||||
Humidity | 15%~90% | ||||||
Dimensions(W×D×H)mm | 145×400×220 | 192×460×340 | |||||
Net Weight(Kg) | 14 | 7 | 34 | 13.5 | 34.5 | 14 |