MODEL (PW Series) |
HV Model | |||
PW8-12KW HV(230Vac) | ||||
Line Mode Specifications: | ||||
Input Voltage | Input Voltage Waveform | Sinusoidal (utility or generator) | ||
Nominal Input Voltage | 230Vac | |||
Low Line Disconnect | 184Vac±4% | |||
Low Line Re-connect | 194Vac ±4% | |||
High Line Disconnect | 263Vac±4% | |||
High Line Re-connect | 253Vac±4% | |||
Max AC Input Voltage | 270Vrms | |||
Input Frequency |
Nominal Input Frequency |
50Hz/ 60Hz (Auto detection) | ||
Low Line Frequency Re-connect |
51+0.3Hz for 60Hz; 41+0.3Hz for 50Hz; |
|||
Low Line Frequency Disconnect |
50+0.3Hz for 60Hz; 40+0.3Hz for 50Hz; |
|||
High Line Frequency Re-connect |
64+0.3Hz for 60Hz; 54+0.3Hz for 50Hz; |
|||
High Line Frequency Disconnect |
65+0.3Hz for 60Hz; 55+0.3Hz for 50Hz; |
|||
main functions |
Output Voltage Waveform | As same as Input Waveform | ||
Over-Load Protection (SMPS load) |
Fuse | |||
Output Short Circuit Protection |
Fuse | |||
Transfer Switch Rating | 63A/80A/100A | |||
Max Bypass Overload Current |
100A | |||
Battery Invert Mode Specifications: | ||||
output | Output Voltage Waveform | Sine wave | ||
Rated Output Power (KW) | 8kw/10kw/12kw | |||
Power Factor | 0.9~1.0 | |||
Nominal Output Voltage (V) |
230Vac ±10% rms | |||
Nominal Output Frequency (Hz) |
60Hz ± 0.3Hz 50Hz ± 0.3Hz |
|||
DC Voltage |
Nominal DC Input Voltage | 48V/72V | ||
DC Voltage range | 40-62Vdc for 48VDC/ 70-93Vdc for 72VDC | |||
Low Battery Alarm | 42.0Vdc ± 1.2Vdc for 48V battery 63.0Vdc ± 1.8Vdc for 72V battery |
|||
Low DC input Shut-down |
40.0Vdc ± 1.2Vdc for 48V battery 60.0vdc± 1.8Vdc for 72V battery |
|||
High DC input Alarm & Fault |
64Vdc ± 1.2Vdc for 48V battery 96Vdc ± 1.8Vdc for 72V battery |
|||
High DC input Recovery |
62.0Vdc ± 1.2Vdc for 48V battery 93.0Vdc ± 1.8Vdc for 72V battery |
|||
Charger | Nominal Charge Current |
35A/50A(5 stages adjustable charging current) |
||
Charge Current Regulation |
± 5Adc | |||
Over Charge Protection |
Bat. V ≥62Vdc / 93Vdc, beeps 0.5s every 1s & fault after 60s |
|||
Algorithm | Three stage: Boost CC (constant current stage) → Boost CV (constant voltage stage) → Float (constant voltage stage) |
|||
Efficiency | Efficiency (Battery Mode) | ≥85% | ||
Efficiency (Line Mode) | >98% | |||
Transfer Time |
Ac to Dc | 20ms (Max) | ||
Dc to Ac | 15ms (Max) | |||
System parameter |
Over-Load Protection | 110% <load<150%, beeps 0.5s every 1s, and Fault after 60s off the output, Load>150%, beeps 0.5s every 1s, and Fault after 20s. |
||
Output Short Circuit Protection |
Current limit (Fault after 10s) | |||
Surge rating (10s) | 1:3 (VA) | |||
Power saver | Load <=25W (Enabled on "P/S auto" setting of Remote control) |
|||
Protections | Low battery, over charging, over load , over temp. |
|||
Indicators | LED+LCD Display | |||
General Specifications |
Operating Temperature Range |
0°C to 40°C | ||
Storage temperature | -15ºC ~60ºC | |||
Operation humidity | 5% to 95%(non-condensing) | |||
Audible Noise | 60dB max | |||
Cooling | Forced air, variable speed fan | |||
Dimension(L*W*H) | 538*255*630mm | |||
Net weight(Kg) | 8KW | 10KW | 12KW | |
60kg | 65.5kg | 71kg |