Model Parameters | PSC3K-24 | PSC5K-48 | PSC5K-96 | |
AC Input |
Nominal Power | 3KVA/2400W | 5KVA/4200W | 5KVA/4200W |
Input Voltage Waveform | Sinusoidal (utility or generator) | |||
Nominal input Voltage | 230VAC | |||
Low Line Disconnect | 170Vac±4%(Normal) or 90Vac±4%(Wide &Generator) | 170Vac±4%(Normal) or 90Vac±4%(Wide &Generator) | ||
Low Line Re-connect | 180Vac±4%(Normal) or 100Vac±4%(Wide &Generator) | 180Vac±4%(Normal) or 100Vac±4%(Wide& Generator) | ||
High Line Disconnect | 280Vac±4%(Normal) or 280Vac±4%(Wide& Generator) | 280Vac±4%(Normal) or 280Vac±4%(Wide &Generator) | ||
High Line Re-connect | 270Vac±4%(Normal) or 270Vac±4%(Wide& Generator) | 270Vac±4%(Normal) or 270Vac±4%(Wide &Generator) | ||
Max AC input Voltage | Max:300VAC | |||
Frequency | 50Hz/60Hz(Auto detection) | |||
AC output |
Output Voltage Waveform | Sine wave | ||
Power Factor | 0.8 | 0.84 | ||
Nominal Output Frequency (Hz) | 50Hz / 60Hz ± 1Hz | |||
Capable of starting electric motor | 1.5HP | 2.5HP | ||
Full load efficiency | ≥90% | |||
AC Charger |
Nominal Charger Current | 10A @Vi/p<170Vac; 20A @ Vi/p=230Vac; 10A @ Vi/p>280Vac); | 20A(95-175V,gen/ wide ,only); 35A(175-275V)@35A setting); 20A(175-275V)@20A) setting); | 10A(95-175V,gen /wide ,only); 20A(175-275V)@20A setting); 10A(175-275V)@10A setting); |
Over charge Protection | 30VDC | 60VDC | 120VDC | |
Floating Charge Voltage | 27VDC | 53.6VDC | 108VDC | |
Battery Voltage |
Nominal DC input Voltage | 24VDC | 48VDC | 96VDC |
Low Battery Alarm | 21VDC | 42VDC | 84VDC | |
High DC input Alarm & Fault | 30VDC | 60VDC | 120VDC | |
Transfer Time | Normal range : 10ms (typical) 15ms (max) Generator/wide range: 20ms (typical) 40ms (max) | |||
System Parameter |
Over-Load Protection | 110% | ||
Output Short Circuit Protection | Current limit (Fault after 4 cycles max) | |||
Protections | Low battery, over charging, over load, over temp | |||
General Specifications |
Operating Temperature Range | 0ºC to 40ºC | ||
Storage Temperature | -15ºC~60ºC | |||
Audible Noise | 60dB max | |||
cooling | Forced air, variable speed fan | |||
Dimension(L*W*H) | 326*268*88.8mm | 456*356.8*118mm | ||
Net Weight(kg) | 5.6 | 11.1 | 12 |