Customization: | Available |
---|---|
Nature of Source Flow: | Passive inverter |
Certification: | ISO9001 |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Model Parameters | GW Plus4KW | GW Plus5KW | GW Plus6KW | |
AC Input |
Nominal Power | 4000W | 5000W | 6000W |
Input Voltage Waveform | Sinusoidal (utility or generator) | |||
Nominal input Voltage | 120/230VAC | |||
Low Line Disconnect | 85Vac±4%(Normal) or 80Vac±4% (Wide) for 120V 184Vac±4%(Normal) or 135Vac±4%(Wide) for 230V | |||
Low Line Re-connect | 95Vac±4%(Normal) or 85Vac±4% (Wide) for 120V 194Vac±4%(Normal) or 145Vac±4%(Wide) for 230V | |||
High Line Disconnect | 136Vac±4%(Normal) or 140Vac±4%(Wide) for 120V 263Vac±4%(Normal) or 263Vac±4%(Wide) for 230V | |||
High Line Re-connect | 131Vac±4%(Normal) or 135Vac±4% (Wide) for 120V 253Vac±4%(Normal) or 253Vac±4%(Wide) for 230V | |||
Max AC input Voltage | 120V for Max150V / 230V for Max270V | |||
Frequency | 50Hz:41-54Hz / 60Hz:51-64Hz | |||
AC output |
Output Voltage Waveform | Sine wave | ||
Power Factor | 0.9~1.0 | |||
Nominal Output Voltage (V) | LV:120Vac ±10%rms / HV:230Vac ±10%rms | |||
Nominal Output Frequency (Hz) | 50Hz ± 0.3Hz / 60Hz ± 0.3Hz | |||
Transfer Time | 20ms(max) | |||
Solar charger |
Rated Charge Current | 60A | ||
PV Input Voltage range | 30VDC-55VDC for 24VDC / 60-110VDC for 48V | |||
Max.PV open circuit array voltage | 24V for 55Vdc,48V for 110Vdc | |||
Charger mode | MPPT | |||
Efficiency | ≥97% | |||
AC Charger |
Nominal Charger | 35A/50A/70A/90A(According to the inverter model) | ||
Current | 5 stages adjustable charging current | |||
Over charge Protection | Bat.V≥31.0VDC for 24V battery,Bat.V≥62.0VDC for 48V battery,beeps 0.5s every 1s & fault after 60s | |||
Efficiency | Efficiency(Battery Mode) | ≥87% | ||
Efficiency (Line Mode) | >98% | |||
Battery Voltage |
Nominal DC input Voltage | 24/48VDC | ||
Low Battery Alarm | 21VDC±0.6VDC for 24VDC | |||
42VDC±1.2VDC for 48VDC | ||||
High DC input Alarm & Fault | 32VDC±0.6VDC for 24VDC | |||
64VDC±1.2VDC for 48VDC | ||||
System Paramete |
Over-Load Protection | 110%150% beeps 0.5s every 1s and Fault after 20s | ||
Output Short Circuit Protection | Current limit (Fault after 10s) | |||
Surge Rating(10s) | 1:3(VA) | |||
Protections | Low battery, over charging, over load, over temp | |||
General Specifications |
Storage Temperature | -15ºC~60ºC | ||
Audible Noise | 60dB max | |||
cooling | Forced air, variable speed fan | |||
Dimension(L*W*H) | 530*396*190mm | |||
Net Weight(kg) | 29.8 | 35 | 40 |