Customization: | Available |
---|---|
Phase: | Single Phase |
Type: | On-line |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Model | DX6K | DX6KL | DX10K | DX10KL | DX3110KL | DX3115KL | DX3120KL | ||
Dimension(W× D× H) | 248× 500 × 616 |
240× 500 × 460 |
248× 500× 616 | 240× 500× 460 | 248× 500× 616 | ||||
Net Weight(kg) | 57 | 18 | 67.5 | 20 | 27 | 35 | 35 | ||
Power | |||||||||
Apparent Power /Active Power |
6KVA/ 4.8KW | 6KVA/ 4.8KW | 10KVA /8KW | 10KVA /8KW | 10KVA /8KW | 15KVA /12KW | 20KVA /16KW | ||
Mains | |||||||||
VoltageRange | 120VAC--275VAC | 210~475VAC | |||||||
Current* | 33Amax | 37Amax | 55Amax | 59Amax | 86Amax | 112Amax | |||
Frequency Range | 46Hz--54Hz | ||||||||
Power Factor | 0.99 | 0.95 | |||||||
Output | |||||||||
Voltage | 220VAC× (1± 1%) | ||||||||
Current | 27A | 45A | 68A | 91A | |||||
Frequency | 46Hz--54Hz(Line Mode, Same as input frequency), 50Hz× (1± 0.1%)(Battery Mode) | ||||||||
Power Factor | 0.8 | ||||||||
Overload Capability | 105%--125%, 1 minutes minimum, then transfer to bypass and alarm, Bypass over load > 30 minutes then turn off output. 125%--135%, 30 seconds minimum, then transfer to bypass and alarm, Bypass over load > 1 minutes then turn off output; > 135%, 0.5 seconds minimum, then transfer to bypass and alarm. |
||||||||
Crest Factor | 3: 1 | ||||||||
THD | THD< 2% ( Linear Load) | ||||||||
Battery (High ambient temperature shortens the battery' s lifetimes) | |||||||||
Backup Time | 4minutes (Full Load) | Depend on the capacity of external battery | 3minutes (Full Load) | Depend on the capacity of external battery | |||||
Recover Time | < 7 Hours Comeback to 90% | Depend on the capacity of external battery | < 7 Hours Comeback to 90% | Depend on the capacity of external battery | |||||
Model | DX6K | DX6KL | DX10K | DX10KL | DX3110KL | DX3115KL | DX3120KL |
EMC | |||||||
ESD | IEC61000-4-2 Level 4 | ||||||
RS | IEC61000-4-3 Level 3 | ||||||
EFT | IEC61000-4-4 Level 4 | ||||||
Surge | IEC61000-4-5 Level 4 | ||||||
Operating Temperature | 0º C--40º C | ||||||
Storage Temperature | -25º C--55º C | ||||||
Humidity | 20%--90% | ||||||
Altitude | < 1000m |
Altitude(m) | 1000 | 1500 | 2000 | 2500 | 3000 | 3500 | 4000 | 4500 | 5000 |