Customization: | Available |
---|---|
Nature of Source Flow: | Active Inverter |
Certification: | CCC, ISO9001, RoHS, CE, SAA |
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
|
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Model Parameters | PW 8K | PW 10K | PW 12K | |
AC Input | Nominal Power | 8KW | 10KW | 12KW |
Input Voltage Waveform | Sinusoidal (utility or generator) | |||
Nominal input Voltage | 230VAC | |||
Low Line Disconnect | 184Vac±4% | |||
Low Line Re-connect | 194Vac±4% | |||
High Line Disconnect | 263Vac±4% | |||
High Line Re-connect | 253Vac±4% | |||
Max AC input Voltage | 270Vrms | |||
Frequency | 50Hz:41-54Hz , 60Hz:51-64Hz | |||
AC Output | Output Voltage Waveform | Sine wave | ||
Power Factor | 0.9~1.0 | |||
Nominal Output Voltage (V) | 230Vac ±10%rms | |||
Nominal Output Frequency(Hz) | 60Hz ± 0.3Hz,50Hz ± 0.3Hz | |||
Efficiency | Efficiency(Battery Mode) | ≥85% | ||
Efficiency(Line Mode) | >98% | |||
DC Voltage | Nominal DC input Voltage | 48/72VDC | ||
DC Voltage range | 42-62Vdc for 48VDC,60-93Vdc for 72VDC | |||
Low Battery Alarm | 42VDC±1.2VDC for 48VDC | |||
63VDC±1.8VDC for 72VDC | ||||
Low DC input shut-down | 40VDC±1.2VDC for 48VDC | |||
60VDC±1.8VDC for 72VDC | ||||
High DC input Alarm & Fault | 64VDC±1.2VDC for 48VDC | |||
96VDC±1.8VDC for 72VDC | ||||
High DC input Recovery | 62VDC±1.2VDC for 48VDC | |||
93VDC±1.8VDC for 72VDC | ||||
Transfer Time | AC to DC | 20ms(max) | ||
DC to AC | 15ms(max) | |||
Charger | Nominal Charger Current | 35A/50A(adjustable 5 stages charging current) | ||
Over charger Protection | Bat.V≥62Vdc/93V,beeps 0.5s every 1s &fault after 60s | |||
System Parameter |
Over-Load Protection | 110%<load<150%,beeps 0.5s every 1s,and Fault after 60s off the output, load>150%,beeps 0.5s every 1s,and Fault after 20s | ||
Output Short Circuit Protection | Current limit (Fault after 10s) | |||
Surge Rating(10s) | 1:3(VA) | |||
Power Saver | Load≤25W(Enabled on "P/S auto "Setting of Remote control) | |||
Protections | Low battery, over charging ,over load ,over temp | |||
Indicators | LED+LCD Display | |||
General Specifications |
Operating Temperature Range | 0ºC~40ºC | ||
Storage Temperature | -15ºC~60ºC | |||
Operation humidity | 5% to 95%(non-condensing) | |||
Audible Noise | 60dB max | |||
cooling | Forced air, variable speed fan | |||
Dimension(L*W*H) | 550*255*630mm | |||
Net Weight(kg) | 60.10 | 65.50 | 71.20 |