Still deciding? Get samples of $ !
Request Sample
|
| Customization: | Available |
|---|---|
| Nature of Source Flow: | Active Inverter |
| Certification: | CCC, ISO9001, RoHS, CE, SAA |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency


|
Model |
LW1000 |
LW2000 |
LW3000 |
LW4000 |
LW5000 |
LW6000 |
|
|
AC Input |
Nominal Power |
1000W |
2000W |
3000W |
4000W |
5000W |
6000W |
| Voltage |
120VAC/230VAC |
230VAC |
|||||
| Acceptable Voltage |
194-243VAC/164-243VAC(wide mode) |
||||||
| Line low Transfer |
85V±4%/184(154 wide mode±4% ) |
||||||
| Line low Return |
95V±4%/194(164 wide mode±4% ) |
||||||
| Line high Transfer |
135V±4%/253±4% |
||||||
| Line high Return |
127V±4%/243±4% |
||||||
| Frequency |
50Hz or 60Hz (auto sensing) |
||||||
| Line low Transfer |
47Hz for 50Hz, 57Hz for 60 Hz |
||||||
| Line high Transfer |
55Hz for 50Hz, 65Hz for 60 Hz |
||||||
|
Out Input |
Phase &waveform |
Pure Sine Wave(bypass mode sync to input) |
|||||
| Voltage |
100/110/120/130VAC, 208/220/230/240VAC (bypass mode sync to input) |
||||||
| Voltage Regulation |
±10%rms(bypass mode sync to input) |
||||||
| Frequency |
50Hz±0.3Hz(bypass mode sync to input) |
||||||
| Peak Power |
3 times of rating power |
||||||
| Short Circuit Protection |
Yes, shutdown after 10ms |
||||||
| Power Factor |
0.9-1.0 |
||||||
|
DC Input |
Battery Voltage |
12V/24V/48V |
24V/48V |
||||
| Minimum Start Voltage |
10V for 12V, 20V for 24V, 40V for 48V |
||||||
| Low Battery Alarm |
10.5V for 12V, 21V for 24V, 42V for 48V |
||||||
| Low Battery Transfer |
10V for 12V, 20V for 24V, 40V for 48V |
||||||
| High Voltage Alarm |
16V for 12V, 32V for 24V,64V for 48V |
||||||
| Max Charging Current |
20A/35A/70A/90A |
||||||
| Over charge Voltage |
15.7V for 12V,31.4V for 24V, 62.8V for 48V |
||||||
|
Transfer Efficiency |
Line Mode |
>95% |
|||||
| Battery Mode |
>88% |
||||||
| Power saver |
Available when the load is less than 25 Watts |
||||||
|
Indicators |
Switch selector |
Saving Mode is on/off when push the switch forwards/backwards , |
|||||
| Audible Alarm |
Sounding when the heatsink's tem is over 105ºC and shutdown after 30 seconds. |
||||||
| Protections |
low battery/ over charging /over temp/over load |
||||||
| Communications |
RS-232/USB(custom-made) |
||||||
|
Enviromental |
Operating Environment |
0-40ºC,0-90%ºC RH(non-condensing) |
|||||
| Audible Noise |
<60dB |
||||||
| Net Weight (KG) |
18 |
20 |
22 |
35 |
38 |
40 |
|
| Dimension (LxWxH) |
446×218×179mm |
605×218×179mm |
|||||