Customization: | Available |
---|---|
Phase: | Three Phase |
Type: | On-line |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Power Rating | 60kVA | 80kVA | 90kVA | 100kVA | 120kVA | 150kVA | 200kVA | 250kVA | 300kVA | 400KVA | 500KVA |
Main Input | |||||||||||
Grid System | 3 Phases + Neutral + Ground | ||||||||||
Rated Input Voltage | 380/400/415VAC | ||||||||||
Rated Frequency | 50/60Hz | ||||||||||
Input Voltage Range | 304~478Vac (Line-Line),full load 228V~304Vac (Line-Line),load decrease linearly according to the min phase voltage |
||||||||||
Input Frequency Range | 40Hz~70Hz | ||||||||||
Input Power Factor | >0.99 | ||||||||||
Input Current THDi | <3% (full Linear Load) | ||||||||||
Bypass Input | |||||||||||
Rated Bypass Voltage | 380/400/415VAC (Line-Line) | ||||||||||
Rated Frequency | 50/60Hz | ||||||||||
Bypass Voltage Range | Selectable, default -20%~+15% Up limited: +10%, +15%, +20%, +25% Down limited: -10%, -15%, -20%, -30%, -40% |
||||||||||
Bypass Frequency Range | Selectable, ±1Hz, ±3Hz, ±5Hz | ||||||||||
Bypass Overload | 125%, long time operation 125%< load <130%, last for more than 10 minutes 130%<load<150%,last for more than 1 minutes >150%, last for more than 300ms |
110% Long term operation 110%~125% last for more than 5min 125%~150% last for more than 1min >150% last for more than 1s |
|||||||||
Output | |||||||||||
Rated Inverter Voltage | 380/400/415VAC (Line-Line) | ||||||||||
Rated Frequency | 50/60Hz | ||||||||||
Output Power Factor | 0.9 | ||||||||||
Voltage precision | ±2% | ||||||||||
Transient Response | <5% for step load (20% - 80% -20%) | ||||||||||
Transient recovery | < 30ms for step load (0% - 100% -0%) | ||||||||||
Output Voltage THDu | <1.5% from 0% to 100% linear load <6% full non-linear load according to IEC/EN62040-3 |
||||||||||
Inverter Overload | <110%, 60min; 110%~125%,10min; 125%~150%,1min; >150%,200ms |
||||||||||
Frequency Regulation | 50/60Hz±0.01% | ||||||||||
Synchronized Range | Settable, ±0.5Hz ~ ±5Hz, default ±3Hz | ||||||||||
Synchronized Slew Rate | Settable, 0.5Hz/S ~ 3Hz/S, default 0.5Hz/S | ||||||||||
Battery And Charger | |||||||||||
Battery Rate Voltage | ±240VDC | ||||||||||
Charger Voltage precision | 1% | ||||||||||
Charger Power | max=20% *Output power | ||||||||||
Efficiency | |||||||||||
Normal Operation | >95% | >96% | >95% | >96% | >95% | >96% | |||||
Battery Operation | >95% | >96% | >95% | >96% | >95% | >96% | |||||
System | |||||||||||
Display | LED + LCD + touch screen | ||||||||||
Interface | RS232, RS485, USB,Programmable dry contact | RS232, RS485, USB,Programmable dry contact,battery cold start | |||||||||
Option | battery cold start,SNMP,AS400,parallel kit,Lightning protection components,Dust Filter,LBS | SNMP,AS400,parallel kit,Lightning protection components,Dust Filter,LBS | |||||||||
Environmental | |||||||||||
Operation Temperature | 0 ~ 40 ºC | ||||||||||
Storage Temperature | -40 ~ 70 ºC | ||||||||||
Relative Humidity | 0 ~ 95% Non condencing | ||||||||||
Noise (1 meter) | 65dB @ 100% load, 62dB @ 45% load | ||||||||||
Altitude | <1000m, Load derated 1% per 100m From 1000 ~ 2000m | ||||||||||
Phisical data | |||||||||||
Cabinet Dimension(W*D*H,mm) | 600*980*950 | 600*980*1150 | 600*980*1400 | 600*980*1150 | 600*980*1400 | 650*960*1600 | 650*960*1600 | 650*960*2000 | 650*960*2000 | 1300*1100*2000 | 1300*1100*2000 |
Cabinet Weigh (kg) | 170 | 210 | 231 | 210 | 266 | 305 | 350 | 445 | 490 | 810 | 900 |